JST's Heated Filtered bath continuously filters process chemicals in a laminar flow direction from the bottom of the bath upward over a four sided weir. The bath is design to filter sub-micron particles and reduce chemical consumption.
A 12 inch inline filter housing accepts a standard 10 inch dual o-ring filter cartridge allowing users to install the type of filter cartridge they need depending on chemistry PH and particle removal size required.
Baths are available in 316L stainless steel or quartz with serrated overflow edges for uniformity.
The heating elements are bonded to the outer walls, insulated and contained with an outer shroud. The heating element in the double wall housing is N2 purge. Inline heaters are recommended for large, high temperature baths that require a fast heat up time.
A PID controller using a Type J RTD temperature probe controls the bath temperature. The controller has a programmable temperature and timer. An audio alarm sounds if the bath goes out of the specified operating temperature. In an over temperature condition the controller will turn off the heaters. A heating element snap switch protects an over temperature condition in case the controller or probe fail. A liquid level detection monitors the chemistry level in the bath to keep a safe operating level. |